AZCL series smart capacitor
时间: 2018-10-19 14:55 浏览次数: 来源:澳门网站大全网址平台

  1 Overview

  AZCL series smart capacitors are a new generation of reactive power compensation equipment used in 0.4kV, 50Hz low voltage power distribution to save energy, reduce line loss, improve power factor and power quality. Among them, the products with 7% reactors are used in the electrical environment with the main harmonics of 5 times, 7 times and above, and the products with 14% reactors in series are used in the electrical environment with the main harmonics of 3 times and above.

  Features: zero-crossing, phase-separation compensation, temperature protection, phase loss protection, overvoltage, undervoltage protection, harmonic function, intelligent network control, high reliability, building block structure, simple wiring, convenient expansion, easy maintenance, The effect is remarkable.

  2. Model Description



  3. Specifications


  4. Scheme wiring diagram



不带终端的共补接线图


  5. Product application plan

  5.1 Three-phase compensation application scheme with transformer capacity of 100/125/160/200/250/315/400/800/1000/1250/1600/2000KVA

  Design scheme: three-phase compensation, voltage zero-crossing input, current zero-crossing

  The compensation capacity is configured according to 50% of the total capacity of the transformer. If the compensation capacity is insufficient, the number of capacitors can be appropriately increased;

  When the compensation capacity is configured, it is configured as a trapezoidal compensation method to improve the compensation accuracy.

  The controller and the indicator can be selected or selected one by one. If the indicator is not used, the traditional indicator light can be connected;

  Main applications: residential projects, urban networks, rural power grid reconstruction projects, and three-phase balanced power applications where harmonics do not exceed the standard.




  5.2 Single-phase and three-phase hybrid compensation application scheme with transformer capacity of 100/125/160/200/250/315/400/800/1000/1250/1600/2000KVA

  Design scheme: three-phase compensation, voltage zero-crossing input, current zero-crossing

  The compensation capacity is configured according to 50% of the total capacity of the transformer, and the total compensation is 30~40%. If the compensation capacity is not enough, the number of capacitors can be appropriately increased;

  When the compensation capacity is configured, it is configured as a trapezoidal compensation method to improve the compensation accuracy.

  The controller and the indicator can be selected or selected one by one. If the indicator is not used, the traditional indicator light can be connected;

  Main applications: residential projects, urban networks, rural power grid reconstruction projects, and three-phase balanced power applications where harmonics do not exceed the standard.




  5.3 Three-phase compensation application scheme with transformer capacity of 100/125/160/200/250/315/400/800/1250/1600/2000KVA (series 7% reactor)

  Design scheme: three-phase compensation, voltage zero-crossing input, current zero-crossing

  The compensation capacity is configured according to 50% of the total capacity of the transformer. If the compensation capacity is insufficient, the number of capacitors can be appropriately increased.

  When the compensation capacity is configured, it is configured as a trapezoidal compensation method to improve the compensation accuracy.

  The controller and the indicator can be selected or selected one by one. If the indicator is not used, the traditional indicator light can be connected;

  7% series of anti-harmonic power capacitors are mainly used for reactive power compensation in residential areas, urban networks, enterprises and other industries with relatively stable 5th and 7th harmonics. 14% series of anti-harmonic power capacitors are mainly used in 3, 5, 7th harmonic exceeded the standard, the load is relatively stable, metallurgical casting, machining, large steel mills and other industries reactive power compensation.





  5.4 Single-phase and three-phase hybrid compensation application scheme with transformer capacity of 100/125/160/200/250/315KVA

  Design scheme: three-phase compensation, voltage zero-crossing input, current zero-crossing

  The compensation capacity is configured according to 50% of the total capacity of the transformer, and the total compensation is 30~40%. If the compensation capacity is not enough, the number of capacitors can be appropriately increased;

  When the compensation capacity is configured, it is configured as a trapezoidal compensation method to improve the compensation accuracy.

  The controller and the indicator can be selected or selected one by one. If the indicator is not used, the traditional indicator light can be connected;

  7% series of anti-harmonic power capacitors are mainly used for reactive power compensation in residential areas, urban networks, enterprises and other industries with relatively stable 5th and 7th harmonics. 14% series of anti-harmonic power capacitors are mainly used in 3, 5, 7th harmonic exceeded the standard, the load is relatively stable, metallurgical casting, machining, large steel mills and other industries reactive power compensation.